Model |
ENC-A2900L |
Type |
Lateral-mount type |
Cooling scheme |
Compressor |
Cooling capacity (W) |
2600/2900(50/60Hz) |
Power supply (50/60Hz) |
3 phase 200VAC±10% |
Current consumption (A)(MAX) |
5.7/5.6 |
Starting current (A) |
31.0/30.0 |
Power consumption (W)(MAX) |
1500/1650 |
Allowable ambient temperature (ºC) |
20 to 55 |
Allowable ambient humidity (%) |
10 to 85 (No condensation) |
Refrigerant |
R-134a (A kind of freon that is not prohibited) |
Temperature setting range (ºC) |
25 to 45 |
Number of fans |
4 |
Output |
Output of operation & alarm(250V 2A) |
Display |
LED Temperature/Error RUN |
Noise immunity |
Level 4 in the fast transient/Burst immunity test |
Noise (dB) |
Approx. 75/79 |
Vibration resistance |
Vibration frequency : 5Hz ; a double amplitude of 20mm |
Paint color |
Munsell 5Y7/1 Equivalent color of light beige |
Outer dimensions (mm) |
H1380×W450×D230 |
Weight(kg) |
55 |