Model |
ENC-2200EX-UL |
Type |
Ceiling-mount type |
Cooling scheme |
Compressor |
Cooling capacity (W) |
1900/2200 |
Power supply (50/60Hz) |
3 phase 200VAC±10% |
Current consumption (A)(MAX) |
3.1/3.1 |
Starting current (A) |
13/12 |
Power consumption (W)(MAX) |
840/950 |
Allowable ambient temperature (ºC) |
20 to 55 |
Allowable ambient humidity (%) |
10 to 85 (No condensation) |
Refrigerant |
R-134a(A kind of freon that is not prohibited) |
Operation control scheme |
Microcomputer-based automatic control |
Temperature setting range (ºC) |
25 to 45 |
Number of fans |
3 |
Noise immunity |
Level 2 in the fast transient/Burst immunity test |
Vibration resistance |
2 |
Vibration resistance |
Vibration frequency : 5Hz ; a double amplitude of 20mm |
Paint color |
Munsell 5Y7/1 Equivalent color of light beige |
Outer dimensions(mm) |
H447×W650×D400 |
Weight(kg) |
35 |