Model |
ENC-1010L-LND |
Type |
Outdoors lateral-mount type |
Cooling scheme |
Compressor |
Cooling capacity (W) |
900/1000 (50/60Hz) |
Power supply (50/60Hz) |
1 phase 100VAC ±10% |
Current consumption (A)(MAX) |
7.0/7.5 |
Starting current (A) |
15.6/14.7 |
Power consumption (W)(MAX) |
630/740 |
Allowable ambient temperature (ºC) |
-5 to 50 |
Allowable ambient humidity (%) |
10 to 80 (No condensation) |
Operation control scheme |
Microcomputer-based automatic contorl |
Refrigerant |
R-134a(A kind of freon that is not prohibited) |
Temperature setting range (ºC) |
25 to 45 |
Number of fans |
6 |
Output |
Alarm output |
Display |
Temperature/Error |
Noise immunity |
Level 2 in the fast transient : Burst immunity test |
Noise |
Approx. 55/57 dB |
Vibration resistance |
Vibration frequency : 5Hz : a double amplitude of 20mm |
Paint color |
Munsell 5Y7/1 Equivalent color of light beige |
Enclosure rating |
Corresponding to IP54 (Internal circulation course) |
Outer dimensions (mm) |
H800×W500×D250 |
Weight(kg) |
40 |