Home > ANYWIRE DB Master Unit > AG42-D1 |
Open network DeviceNet |
I/O number | Four-all pile mode: 992 points or less (Bit-Bus: 512 points or less/Word-Bus: 512 points or less) |
||||||||||||||||||||
AnyWireBus port | One port and detachable terminal stand | ||||||||||||||||||||
Connected the number | 128 or less | ||||||||||||||||||||
Transmission distance | The total extension 100m, 200m, 500m, and 1km are selected. | ||||||||||||||||||||
Transmission speed | 7.8kHz,15.6kHz,31.3kHz,62.5kHz | ||||||||||||||||||||
Transmission cycle time Unit[msec] (one cycle time value) |
|
||||||||||||||||||||
RAS function | Transmission line disconnection position detection function and transmission line short-circuit detection function Transmission power supply decrease detection function |
||||||||||||||||||||
Connecting cable | Two general-purpose wicks/4 Wick cable (VCTF 0.75-1.25sq) Special flat cable (0.75sq) and general-purpose electric wire(0.75~1.25sq) |
||||||||||||||||||||
Power supply | +24V +15%-10% ripple 0.5Vp-p or less Current about 0.2A Max. (When 128 in the terminal is connected, the load current is not included. ) |
||||||||||||||||||||
Ambient temperature of use | 0℃~+55 ℃ (preservation temperature :- 20℃-+75℃) | ||||||||||||||||||||
Use humidity | 10%~90%RH (dewfall) | ||||||||||||||||||||
Atmosphere | Causticity gas and flammable gas |
Agreement DeviceNet specification | Ver.1.2 | ||||||||||||||||
Transmission rate | 500K/250K/125Kbit/s(automatic follow) | ||||||||||||||||
Communication distance |
|
||||||||||||||||
Number of maximum, connected nodes | 64(The number of maximum, connected slaves is 63. ) | ||||||||||||||||
Error control | CRC error, node address repetition check, and collation of scanning list | ||||||||||||||||
Connected connector | MSTB2.5/5-ST-5.08AU(made of [fuenikkusu] contact) | ||||||||||||||||
[Puredefaindomasuta]/Slave connection set | Two group [onrisa-ba] | ||||||||||||||||
I/O size | Produced Connection Size(input size) For input/64 point output mode 64 points――― 10 For input/128 point output mode 128 points―― 18 Consumed Connection Size(output size) For input/64 point output mode 64 points――― 10 For input/128 point output mode 128 points―― 18 |
||||||||||||||||
The maximum current consumption | 40mA |
For more details and information, please visit this www.anywire.jp