ANYWIRE DB Master Unit - AFSR01
|
Fast master debut to micro PLC. FA-M3™ It is possible to connect directly with the series.
AFSR01 FA-M3™ series master interface specification
Correspondence CPU unit |
F3SP21-0N,F3SP25-2N,F3SP28-3N,F3SP35-5N,F3SP38-6N,F3SP53-4H,F3SP58-6H,F3FP36-3N,F3SP28-3S,F3SP38-6S,F3SP53-4S,F3SP58-6S,F3SP59-7S |
I/O number |
4 all pile mode: 2560 or less Point (Bit-Bus: 512 points or less/Word-Bus: 2048 or less point) |
AnyWireBus port |
One port and detachable terminal stand |
Connected the number |
128 or less |
Transmission distance |
The total extension 200m, 500m, and 1km are selected. |
Transmission cycle time Unit[msec] (one cycle time value) |
4 all Pile mode bit bus |
62.5kHz |
31.3kHz |
15.6Hz |
7.8kHz |
64 points |
0.85 |
1.7 |
3.4 |
6.8 |
128 points |
1.4 |
2.7 |
5.4 |
10.9 |
256 points |
2.4 |
4.8 |
9.5 |
19.1 |
512 points |
4.4 |
8.9 |
17.7 |
35.5 |
Four-all pile mode word bus |
62.5kHz |
31.3kHz |
15.6Hz |
7.8kHz |
IN8word/OUT8word |
2.5 |
5.0 |
9.9 |
19.8 |
IN16word/OUT16word |
4.7 |
9.3 |
18.6 |
37.2 |
IN32word/OUT32word |
9.0 |
18.0 |
36.0 |
72.1 |
IN64word/OUT64word |
17.7 |
35.4 |
70.9 |
141.7 |
|
RAS function |
Transmission line disconnection position detection function, transmission line short-circuit detection function, and transmission power supply decrease detection function |
Connecting cable |
Two general-purpose wicks/4 Wick cable (VCTF 0.75-1.25sq)
Special flat cable (0.75sq) and general-purpose electric wire(0.75~1.25sq) |
Power supply |
+5V±5% 0.2A (supply from FA-M3 side) +24V +15%-10% ripple 0.5Vp-p or less Current about 0.2A Max. (When 128 in the terminal is connected, the load current is not included. ) |
Ambient temperature of use |
0℃~+55 ℃ (preservation temperature :- 20℃-+75℃) |
Use humidity |
10%~90%RH (dewfall) |
Atmosphere |
Causticity gas and flammable gas |
For more details and information, please visit this www.anywire.jp
|