Making to conserve wiring in board and in machine.
Two or more signals are consolidated in two lines.


AB00XB


Main body of AB00XB-16U EZwire specification
Kind Main body of Ezwire
Connected specification Screw type terminal stand
I/O number Digital input eight points and digital output eight points
Product model AB00XB-16U
Use power supply DC24V+15--10% ripple 0.5Vp-p or less
About 0.4A or less in current(Neither a terminal load current nor an external load current are contained. )
Input specification Transistor input input resistance: 5.6kΩ and input current: 2.1mA max at 5.1 mA min. OFF when turning it on.
The voltage level between input: 7V max at 16 V min. OFF when turning it on.
Output specification Open collector output   output ON current: 100mA max . /road once
Residual voltage: 1V max and leakage of current: 0.1mA max and electric strength: 30V
Connecting cable Conserve distributing cable: Two general-purpose wicks (VCTF 0.75-2.1mm2) Two general-purpose electric wire wicks( 0.75~2.1mm2)
I/O cable : [Yoshin] 0.32-2.1mm2
Acceptable [acchaku] terminal: Round terminal, 6mm or less in outside diameter of terminal Y, and hole diameter 3.2mm
Connected the number 40 or less
Conserve wiring connection distance 50m or less
Conserve wiring transmission cycle time 1.7 Ms/40 point(one cycle time)
Connection status Bus form
Ambient temperature of use 0~+55℃(-20-+75℃ in preservation temperature)
Use surroundings humidity 10~90%RH(dewfall)
Atmosphere Causticity gas flammability gas
Externals size[mm] 140×40×60
Protection grade IP20


The main specification on CC-Link side
Version CC-Link Ver.1.10/Ver.2.00(switch with switch)
Bureau kind Remote device bureau
Number of occupation bureaux Four games
Remote exchange number Exchange number setting range 1 -61(Become four game occupation from the exchange number setting. )
Number of remote devices Input: 896 point or less output: 896 points or less(The Ver.2.0 8 time is set. )
Input: 112 point or less output: 112 points or less(Ver.1.1)
Remote register point Input: 128 point or less output: 128 points or less(The Ver.2.0 8 time is set. )
Input: 16 point or less output: 16 points or less(Ver.1.1)
Transmission speed 10M/5M/2.5M/625K/156Kbps (switch with switch)
Transmission distance 100m(10Mbps) 160m(5Mbps) 400m(2.5Mbps) 900m(625kbps)
1200m(156kbps)
The CC-Link connection number
(For Ver.1. )
1 × a) + (2 ×b ) + (3 ×c ) + (4 ×d ) ≦64 game The number of a :1 game occupation bureau, the number of b :2 game occupation bureau, the number of c :3 game occupation bureau, and the number of d :4 game occupation bureau
16 ×A +54 ×B +88 ×C ≦2304
A: Remote I/O bureau 64 or less ..number ・・・・・・・・・・・・・・・・・..
B: Remote device bureau 42 or less ..number ・・・・・・・・・・・・..
C: Local bureau 26 or less ..number ・・・・・・・・・・・・・・・・・・・・・..
Connecting cable Cable for CC-Link(3 with shield wick twisted-pair cable)