Kind |
Input |
Connected specification |
Standard terminal stand |
Screw improvement type terminal stand |
I/O number |
16 points |
32 points |
16 points |
32 points |
Product model |
A40SW-01US |
A40SW-02US |
A40SW-01US-1 |
A40SW-02US-1 |
Use power-supply voltage |
C24V+15%~-10% |
Input specification |
Transistor input input resistance: 5.6kΩ and input current: 2.1mA max at 5.1 mA min. OFF when turning it on. The voltage level between input: 7V max at 16 V min. OFF when turning it on. |
Connecting cable |
Transmission cable: [Yoshin] 0.75-2.1mm2 I/O cable : [Yoshin] 0.32-2.1mm2 Acceptable [acchaku] terminal: Round terminal, 6mm or less in outside diameter of terminal Y, and hole diameter 3.2mm |
Communication display |
LED(Blink with the synchronized signal. ) |
State display |
LED(The state of the input is displayed. ) |
Maximum electric power consumption |
5.6W |
10W |
5.6W |
10W |
Transmission scheme |
Four-all pile in total frame cyclic method |
Synchro system |
Frame/bit synchro system |
Transmission procedure |
Special protocol(AnyWireBus) |
Transmission clock/distance |
62.5kHz/100m 31.3kHz/200m 15.6kHz/500m 7.8kHz/1000m |
Connection status |
Bus form |
Fan Inn |
1 |
Number of occupation data |
1 word |
2 words |
1 word |
2 words |
Use range humidity |
10~90%RH (..dewfall.. thing) |
Use range temperature |
0~+55℃ |
Preservation temperature |
-20~ +75℃ |
Atmosphere |
Thing without causticity gas |
Proof vibration |
It conforms to JIS C 0040. |
Impact-proof |
100m/s2 |
Insulation resistance |
Between the relay terminal and the outside box 20MΩ or more. |
Electric strength |
Between the relay terminal and the outside box The AC1000V 1 minute. |
Noise-proof |
1200Vp-p (pulse width 1μs) |
Material |
Main body: PPE・V0 class |
Externals size[mm] |
140×40×60 |
190×40×60 |
140×40×60 |
190×40×60 |
Protection grade |
IP20 |
Mass |
180g |
240g |
225g |
305g |