Kind |
Electric power measurement terminal |
Measurement specification |
Three-phase circuit and three lines . . Expression |
Single phase and three lines. Expression |
Single phase and two lines. Expression |
Number of measurement circuits |
Seven circuits |
Seven circuits |
Seven circuits |
Input factor |
2 voltage × ch 14 current × ch |
2 voltage × ch 14 current × ch |
1 voltage × ch 12 current × ch |
Input specification (voltage element) |
Direct input Either of of the ratings 100/200/440V is selected. (440/220V converter is necessary for 440V. ) |
Input specification (current element) |
Clamping CT input Either of ratings 30/60/120/200/300/500A is selected. |
Product model |
A40SW-J7PW1-1 |
A40SW-J7PW1-2 |
A40SW-J7PW1-3 |
Use power-supply voltage |
DC24V+15%~-10% |
Accuracy |
Please refer to the measurement specification paragraph. |
Communication display |
LED(Blink with the synchronized signal. ) |
Maximum electric power consumption |
3.0W |
Transmission scheme |
Four-all pile in total frame cyclic method |
Synchro system |
Frame/bit synchro system |
Transmission procedure |
Special protocol |
Transmission clock/distance |
62.5kHz/100m 31.3kHz/200m 15.6kHz/500m 7.8kHz/1000m |
Connection status |
Bus form |
Fan Inn |
1 |
Number of occupation data |
Two two output words and input 2/input 4/output words |
Use surroundings humidity |
10-90%RH dewfall |
Ambient temperature of use |
0~+55℃ |
Preservation temperature |
-20~ +75℃ |
Atmosphere |
Causticity gas flammability gas |
Proof vibration |
It conforms to JIS C 0040. |
Impact-proof |
100m/s2 |
Insulation resistance |
Between the relay terminal and the outside box 20MΩ or more. |
Electric strength |
Between the relay terminal and the outside box. The AC1000V 1 minute. |
Noise-proof |
1200Vp-p (pulse width 1μs) |
Material |
Main body: PPE and V0 class |
Externals size[mm] |
190×40×60 |
Protection grade |
IP20 |
Mass |
240g |